Trifásico
UPS Trifásico 40 – 120kVA 3:3
MODEL | KUE-3T40 -NB | KUE-3T60 -NB | KUE-3T80 -NB | KUE-3T120 -NB | ||
INPUT | ||||||
Rated voltage | 380 / 400 / 415 Vac | |||||
Frequency range | 40 ~ 70 Hz | |||||
Power factor | ≥ 0,99 | |||||
Bypass voltaje range | - 60% ~ +20% (settable) | |||||
OUTPUT | ||||||
Voltage | 380 / 400 / 415 Vac | |||||
Voltage regulation | ± 1% | |||||
Frequency | Synchronized with utility in mains mode, 50/60 Hz ± 0.1% in battery mode | |||||
Power factor | 1 | |||||
THDV | ≤ 1% (linear load), ≤ 5% (non – linear load) | |||||
BATTERIES | ||||||
DC voltage | ± 192 Vdc (± 180 ~ ± 276 Vdc settable) | |||||
Charging current (max.) | 12 A | 24 A | 36 A | |||
Recharger time | Dependo n the capacity of battery | |||||
OTHERS | ||||||
Dimensiones (W x D x H) (mm) | 360 x 850 x 950 | 360 x 850 x 1200 | 440 x 850 x 1200 | |||
Operating Temperature | 0°C ~ 40°C | |||||
Altitude | ≤ 1000 m; above 1000m, downgrading 1% for each additional 100m | |||||
UPS Trifásico W 10 KVA – 30KVA
MODEL | W10K | W15K | W20K | W30K | ||
INPUT | ||||||
Rated voltage | 380 / 400 / 415 Vac | |||||
Frequency range | 40-70 | |||||
Power factor | > 0,99 | |||||
Bypass voltaje range | -20 % ~ +15% Up limited_+10%, +15%, +20%, +25%. Down limited: -10%, -15%, -20%,-30%,-40%, | |||||
OUTPUT | ||||||
Voltage | 380/400/415 Vac | |||||
Voltage regulation | ± 1% | |||||
Frequency | Synchronized with utility in mains mode, 50/60 Hz ± 0.1 % in battery mode | |||||
Power factor | 1 | |||||
THDV | ≤ 1% (full linear load), <3% (Full non-linear load according to IEC/EN62040-3) | |||||
BATTERIES | ||||||
DC voltage | ± 120 VDC (20 PCS) | ± 240 VDC (40 PCS) | ± 240 VDC (40 PCS) | ± 180 VDC (60 PCS) | ||
Charging current | 10A max | |||||
Recharger time | Estándar model: 90% capacity restored in 8 hours, Long time model: depend on the capacity of battery. | |||||
OTHERS | ||||||
Dimensiones (W x D x H) (mm) | 250 x 750 x 560 (S) 250 x 750 x 560 (H) | 250 x 800 x 700 (S) 250 x 720 x 560 (H) | 250 x 840 x 930 (S) 250 x 840 x 650 (H) | |||
Operating Temperature | 0°C ~ 40°C | |||||
Altitude | ≤ 1000 m, Load derated 1% per 100m from 1000 – 2000m |
UPS Trifásico MY Series Online UPS 10~40kVA
MODEL | MY10 | MY20 | MY30 | MY40 | ||||||
Input | ||||||||||
Voltage (Vac) | 80-280 (L-N)/138-485 (L-L) | 138-485 (L-L) | ||||||||
Frequency (Hz) | 40-70 | |||||||||
Power Factor | ≥0,99 | |||||||||
THDi | <3% (Carga Lineal) | |||||||||
Output | ||||||||||
Capacity (VA) | 10 | 20 | 30 | 40 | ||||||
AC/AC Efficiency (Max.) | 96% | |||||||||
Power Factor | 1.0 | |||||||||
Voltage (Vac) | 220/230/240±1% (L-N) 380/400/415±1%(L-L) | |||||||||
Frequency (Hz) | 50/60±0,1 (modo batería) | |||||||||
THDv | ≤2% (carga lineal), ≤4% (carga no lineal) | ≤1% (carga lineal), ≤4% (carga no lineal) | ||||||||
Battery | ||||||||||
Voltage (Vdc) | ±192 (±96~±240 ajustable) | ±192 (±144~±240 ajustable)* | ||||||||
BATT Type | 16~40*9AH/12V | 24~40*9AH/12V | 48~80*9AH/12V | |||||||
Charger Current (A) Max. | 1-10 configurable | 1-20 configurable | ||||||||
Other | ||||||||||
Communication Interface | RS485+EPO+Contacto seco (1 entrada, 5 salidas)(SNMP son opcionales en la ranura) | |||||||||
LCD Display | Pantalla Táctil de 4,3 Pulgadas + LED + Botones físicos | |||||||||
Alarm | Baja batería, entrada CA anormal, falla de UPS, etc. | |||||||||
Protection | Baja batería, sobrecarga, cortocircuito y sobretemperatura, etc. | |||||||||
Noise (dB) | <55 | |||||||||
Working Temperature (℃) | -5~40 | |||||||||
Relative Humidity | 0~95%, sin condensación | |||||||||
Dimension (W×D×H) mm | 250×755×880 | 300×785×1250 | ||||||||
Weight (kg) | 98 (20 ×9AH) | 132 (32×9AH) | 240 (64×9AH) | 240 (64×9AH) |
UPS Modular MR33A Series (20~240kVA)
Advanced Technology:
- Online Double Conversion
- Fully DSP control
- N+X parallel technology
- 3 level inverter technology
- DC startup function
- Frequency converter function
- Advanced power module dormancy technology
Excellent Flexibility:
- Intelligent battery management
- Flexible network management
Green Power:
- Wide input voltage range
- PCB boards feature with anti-corrosion paint coating
- Internal maintenance bypass
- Allow 100% three phase unbalance load
- ECO mode and EPO function
- Module communication ring connection redundancy design
- Self-aging test function
UPS FR-UK33 Series Online UPS (10~600kVA)
Main Features
- Online double conversion
- IGBT inverter and output isolation transformer
- Wide input voltage range
- 3 phases UPS allow 100% unbalance load
- Fully DSP control, high reliability and performance
- DC cold start function
- Advanced battery charging management
- Intelligent fan speed control
- HMI-touch screen display
- ECO mode and EPO
- ECO-mode with 98% efficiency
- 10,000 events logs
- Battery self-test function
- Intelligent RS232/RS485,DB9 dry contact communication port
- 10-30kVA models with wheels
- MODBUS &SNMP adapter(optional)
- Advanced no-master-slave parallel technology (optional)
- Intelligent battery monitor system-MMBM(optional)
- 12 Pulse rectifier(optional)
- Bypass isolation transformer(optional)
Application
- Computer room
- Data center
- Precision instrument
- Intelligent equipment
- Industrial application